OPNp · Surge arresters

ОПНп-10 кВ (400А, 600А)

designation given as an exampleCatalog, p. 13SA-10/12/10/600-М12/М12
Series
ОПНп

Technical specifications16 parameters

Parameter1 (400А)2 (600А)
Network voltage class, kV10,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*8,2…12,7
Rated voltage Ur, kV**10,2…15,8
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A400600
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV4,16,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А20,1…31,119,47…30,16
- 250 А20,8…32,220,15…31,2
- 500 А21,53…33,120,83…32,26
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА25,32…39,2624,6…38,1
- 10 кА26,96…41,826,4…40,85
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**27,88…43,127,57…42,7
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N340
Vibration resistance according to ГОСТ 17516.1М6
Creepage distance, not less than, mm420
Mass, kg**1,8

1 (400А)

Network voltage class, kV
10,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
8,2…12,7
Rated voltage Ur, kV**
10,2…15,8
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
400
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
4,1
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
20,1…31,1
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
20,8…32,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
21,53…33,1
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
25,32…39,26
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
26,96…41,8
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
27,88…43,1
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
340
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
420
Mass, kg**
1,8

2 (600А)

Network voltage class, kV
10,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
8,2…12,7
Rated voltage Ur, kV**
10,2…15,8
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
600
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
6,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
19,47…30,16
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
20,15…31,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
20,83…32,26
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
24,6…38,1
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
26,4…40,85
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
27,57…42,7
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
340
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
420
Mass, kg**
1,8
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 13 · Catalog numbers — p. 14 · Drawings — p. 14

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-10/12/10/600-М12/М12 example

Designation structure

Series
ОПНп
Throughput capacity classes
1 (400А), 2 (600А)
Designation (example)
ОПНп-10/12/10/600
Variants in the specification table
1 (400А), 2 (600А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 14

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-10 кВ (400А, 600А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006