Technical specifications16 parameters

Parameter1 (400А)2 (600А)
Network voltage class, kV6,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*5,0…8,0
Rated voltage Ur, kV**6,3…10,0
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A400600
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV4,16,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А12,29…19,611,87…19,0
- 250 А12,71…20,320,3…19,66
- 500 А13,13…21,021,0…20,33
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА15,42…24,715,0…24,0
- 10 кА16,46…26,316,1…25,76
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**16,98…27,216,87…26,9
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N340
Vibration resistance according to ГОСТ 17516.1М6
Creepage distance, not less than, mm320
Mass, kg**1,3

1 (400А)

Network voltage class, kV
6,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
5,0…8,0
Rated voltage Ur, kV**
6,3…10,0
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
400
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
4,1
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
12,29…19,6
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
12,71…20,3
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
13,13…21,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
15,42…24,7
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
16,46…26,3
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
16,98…27,2
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
340
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
320
Mass, kg**
1,3

2 (600А)

Network voltage class, kV
6,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
5,0…8,0
Rated voltage Ur, kV**
6,3…10,0
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
600
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
6,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
11,87…19,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
20,3…19,66
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
21,0…20,33
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
15,0…24,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
16,1…25,76
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
16,87…26,9
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
340
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
320
Mass, kg**
1,3
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 9 · Catalog numbers — p. 10 · Drawings — p. 10

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-6/7,2/10/600-М10/М10 example

Designation structure

Series
ОПНп
Throughput capacity classes
1 (400А), 2 (600А)
Designation (example)
ОПНп-6/7,2/10/600
Variants in the specification table
1 (400А), 2 (600А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 10

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-6 кВ (400А, 600А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006

Request a quote

ОПНп-6 кВ (400А, 600А)

Send us a request — we will confirm the configuration, lead time and price.