Technical specifications16 parameters

Parameter3 (800, 850А)4 (1200А)
Network voltage class, kV35,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*31,0…50,0
Rated voltage Ur, kV**38,7…62,5
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A8001200
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV8,311,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А71,5…115,270,1…112,9
- 250 А73,9…119,272,5..116,9
- 500 А76,4…123,374,9…120,9
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА90,3…145,688,5…142,7
- 10 кА96,8…156,294,9…153,1
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**101,2…163,199,2…160,0
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N365
Vibration resistance according to ГОСТ 17516.1М6
Creepage distance, not less than, mm1700
Mass, kg**14,8

3 (800, 850А)

Network voltage class, kV
35,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
31,0…50,0
Rated voltage Ur, kV**
38,7…62,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
800
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
8,3
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
71,5…115,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
73,9…119,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
76,4…123,3
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
90,3…145,6
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
96,8…156,2
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
101,2…163,1
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
365
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
1700
Mass, kg**
14,8

4 (1200А)

Network voltage class, kV
35,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
31,0…50,0
Rated voltage Ur, kV**
38,7…62,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
1200
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
11,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
70,1…112,9
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
72,5..116,9
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
74,9…120,9
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
88,5…142,7
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
94,9…153,1
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
99,2…160,0
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
365
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
1700
Mass, kg**
14,8
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 23 · Catalog numbers — p. 24 · Drawings — p. 24

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-35/40,5/10/800 example

Designation structure

Series
ОПНп
Throughput capacity classes
3 (800, 850А), 4 (1200А)
Designation (example)
ОПНп-35/40,5/10/800
Variants in the specification table
3 (800, 850А), 4 (1200А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 24

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-35 кВ (800, 850А, 1200А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006

Request a quote

ОПНп-35 кВ (800, 850А, 1200А)

Send us a request — we will confirm the configuration, lead time and price.