OPNp · Surge arresters

ОПНп-27,5 кВ, модификация А (400А, 600А)

designation given as an exampleCatalog, p. 41SA-27,5/30/10/400-А-
Series
ОПНп

Technical specifications16 parameters

Parameter1 (400А)2 (600А)
Network voltage class, kV27,5
Maximum continuous operating voltage of the arrester Uc (rms value), kV*18,5…30,0
Rated voltage Ur, kV**23,1…37,5
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A400600
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV4,16,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А45,33…73,543,94…71,25
- 250 А46,87…76,045,47…73,73
- 500 А48,3…78,047,0…76,22
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА57,25…92,855,5…90,0
- 10 кА60,95…98,859,5…96,48
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**62,9…102,062,2…100,86
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N365
Vibration resistance according to ГОСТ 17516.1М6
Creepage distance, not less than, mm1220
Mass, kg**6,1

1 (400А)

Network voltage class, kV
27,5
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
18,5…30,0
Rated voltage Ur, kV**
23,1…37,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
400
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
4,1
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
45,33…73,5
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
46,87…76,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
48,3…78,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
57,25…92,8
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
60,95…98,8
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
62,9…102,0
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
365
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
1220
Mass, kg**
6,1

2 (600А)

Network voltage class, kV
27,5
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
18,5…30,0
Rated voltage Ur, kV**
23,1…37,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
600
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
6,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
43,94…71,25
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
45,47…73,73
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
47,0…76,22
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
55,5…90,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
59,5…96,48
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
62,2…100,86
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
365
Vibration resistance according to ГОСТ 17516.1
М6
Creepage distance, not less than, mm
1220
Mass, kg**
6,1
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 41 · Catalog numbers — p. 42 · Drawings — p. 42

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-27,5/30/10/400-А- example

Designation structure

Series
ОПНп
Throughput capacity classes
1 (400А), 2 (600А)
Designation (example)
ОПНп-27,5/30/10/400-А
Variants in the specification table
1 (400А), 2 (600А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 42

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-27,5 кВ, модификация А (400А, 600А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006