Technical specifications16 parameters

Parameter1 (400А)2 (600А)
Network voltage class, kV110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*51,0…90,0
Rated voltage Ur, kV**63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A400600
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV4,16,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А124,8…220,2121,0…213,6
- 250 А129,1…125,3125,3…221,0
- 500 А133,0…129,5129,5…228,6
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА157,6…278,1153,0…270,0
- 10 кА168,0…296,5164,0…289,4
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**172,7…304,7171,4…302,4
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N680
Vibration resistance according to ГОСТ 17516.1М1
Creepage distance, not less than, mm3150
Mass, kg**14,5

1 (400А)

Network voltage class, kV
110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
51,0…90,0
Rated voltage Ur, kV**
63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
400
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
4,1
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
124,8…220,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
129,1…125,3
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
133,0…129,5
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
157,6…278,1
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
168,0…296,5
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
172,7…304,7
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
680
Vibration resistance according to ГОСТ 17516.1
М1
Creepage distance, not less than, mm
3150
Mass, kg**
14,5

2 (600А)

Network voltage class, kV
110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
51,0…90,0
Rated voltage Ur, kV**
63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
600
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
6,2
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
121,0…213,6
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
125,3…221,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
129,5…228,6
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
153,0…270,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
164,0…289,4
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
171,4…302,4
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
680
Vibration resistance according to ГОСТ 17516.1
М1
Creepage distance, not less than, mm
3150
Mass, kg**
14,5
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 27 · Catalog numbers — p. 28 · Drawings — p. 28

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-110/73/10/600-А example

Designation structure

Series
ОПНп
Throughput capacity classes
1 (400А), 2 (600А)
Designation (example)
ОПНп-110/73/10/600-А
Variants in the specification table
1 (400А), 2 (600А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 28

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-110 кВ, модификация А (400А, 600А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006

Request a quote

ОПНп-110 кВ, модификация А (400А, 600А)

Send us a request — we will confirm the configuration, lead time and price.