OPNp · Surge arresters

ОПНп-110 кВ (800, 850А, 1200А)

designation given as an exampleCatalog, p. 29SA-110/73/10/800
Series
ОПНп

Technical specifications16 parameters

Parameter3 (800, 850А)4 (1200А)
Network voltage class, kV110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*51,0…90,0
Rated voltage Ur, kV**63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A8001200
Nominal discharge current (amplitude, 8/20 μs), kA10
10 s temporary overvoltage (TOV), Ut/Uc1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV8,311,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV**-125 А117,5…207,4115,2…203,3
- 250 А121,6…214,6119,2…210,4
- 500 А125,7…221,9123,2…217,5
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV**- 5 кА148,5…262,1145,6…257,0
- 10 кА159,2…281,0156,1…275,5
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**166,4…293,6163,4…287,8
Partial discharge level, not more than, pC10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N680
Vibration resistance according to ГОСТ 17516.1М1
Creepage distance, not less than, mm3700
Mass, kg**29,5

3 (800, 850А)

Network voltage class, kV
110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
51,0…90,0
Rated voltage Ur, kV**
63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
800
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
8,3
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
117,5…207,4
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
121,6…214,6
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
125,7…221,9
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
148,5…262,1
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
159,2…281,0
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
166,4…293,6
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
680
Vibration resistance according to ГОСТ 17516.1
М1
Creepage distance, not less than, mm
3700
Mass, kg**
29,5

4 (1200А)

Network voltage class, kV
110,0
Maximum continuous operating voltage of the arrester Uc (rms value), kV*
51,0…90,0
Rated voltage Ur, kV**
63,7…112,5
High-current impulse withstand, 4/10 μs waveform, kA
100
Arrester throughput capacity (amplitude of the 2000 μs rectangular impulse), A
1200
Nominal discharge current (amplitude, 8/20 μs), kA
10
10 s temporary overvoltage (TOV), Ut/Uc
1,41
Energy absorption capability (2 long-duration current impulses, relative to Uc), not less than, kJ/kV
11,0
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV-125 А
115,2…203,3
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 250 А
119,2…210,4
Residual voltage, not more than, at switching surge current, 30/60 μs waveform, with amplitude, kV- 500 А
123,2…217,5
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 5 кА
145,6…257,0
Residual voltage, not more than, at 8/20 μs current impulses for nominal current, kV- 10 кА
156,1…275,5
Residual voltage, not more than, at 1/10 μs steep-front current impulses with 10000 A amplitude, kV**
163,4…287,8
Partial discharge level, not more than, pC
10
Mechanical load from conductor tension, wind and combined ice-and-wind loads, not less than, N
680
Vibration resistance according to ГОСТ 17516.1
М1
Creepage distance, not less than, mm
3700
Mass, kg**
29,5
  • * Maximum continuous operating voltage of the arrester — according to customer requirements.
  • ** Characteristics may vary depending on the maximum continuous operating voltage of the arrester.

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

OPN catalog 2024 (in Ukrainian)

Specifications — p. 29 · Catalog numbers — p. 30 · Drawings — p. 30

Catalog numbers

The maximum continuous operating voltage of the arrester (Uc) is set according to customer requirements, so the catalog gives designations as examples rather than a fixed list of part numbers.

Catalog number
SA-110/73/10/800 example

Designation structure

Series
ОПНп
Throughput capacity classes
3 (800, 850А), 4 (1200А)
Designation (example)
ОПНп-110/73/10/800
Variants in the specification table
3 (800, 850А), 4 (1200А)

Configuration

The configuration of surge arresters is agreed with the customer.

Code structure: upper flange / lower flange / earthing / other

B2.B8.L1.G2 / B8.P3 / B5.Е2.D1 / SС1

Appendix A, pp. 43–44

Drawings

  • Page 30

    OPN catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ОПНп-110 кВ (800, 850А, 1200А).pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

МЭК 60099-4 · ГКД 34.35.512-2002 · ТУ У 31.2-31279430-008:2006