IOSK · Polymer post insulators

ИОСК 4-10-215-4

Insulator ИОСК 4-10-215-4

Catalog, p. 17P.4.10.215.4/R.B36.2М8/0/R.B70.2М10
Series
ИОСК
Voltage class, kV
10
Load class (bending), kN
4
Atmospheric pollution degree
4
Structural height, mm
215

Technical specifications9 parameters

ParameterValue
Nominal voltage, kV10
Mechanical failing load in bending, not less than, kN4,0
Creepage distance, not less than, mm430
Structural height H, mm215
Insulating length L, mm165
Power-frequency withstand voltage for 1 minute, dry/wet, not less than, kV42/28
Lightning impulse withstand voltage, “1.2/50”, not less than, kV75
50% power-frequency flashover voltage in wet and polluted condition, not less than, kVat pollution layer surface conductivity (30±3,0) мкСм13
Mass, kg0,85

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

IOSK catalog 2024 (in Ukrainian)

Specifications — p. 17 · Catalog numbers — p. 18 · Drawings — p. 18

Catalog numbers

Catalog numberPorcelain equivalentFlanges
P.4.10.215.4/R.B36.2М8/0/R.B70.2М10С 4-80-II
upper: D 36 · d М8
lower: D 70 · d М10

Designation structure

Series
ИОСК
Load class (bending), kN
4
Voltage class, kV
10
Structural height, mm
215
Atmospheric pollution degree
4

Drawings

  • Page 18

    IOSK catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ИОСК 4-10-215-4.pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

ТУ У 31.6-31279430-007:2006 · СОУ МПЕ 40.1.51.302

Request a quote

ИОСК 4-10-215-4