IOSK · Polymer post insulators

ИОСК 10-150-1700-4

Insulator ИОСК 10-150-1700-4

Catalog, p. 103P.10.150.1700.4/R.D127.4М16/0/S.D200.4х18
Series
ИОСК
Voltage class, kV
150
Load class (bending), kN
10
Atmospheric pollution degree
4
Structural height, mm
1700

Technical specifications9 parameters

ParameterValue
Nominal voltage, kV150
Mechanical failing load in bending, not less than, kN10,0
Creepage distance, not less than, mm5350
Structural height H, mm1700
Insulating length L, mm1510
Power-frequency withstand voltage for 1 minute, dry/wet, not less than, kV300/300
Lightning impulse withstand voltage, “1.2/50”, not less than, kV650
50% power-frequency flashover voltage in wet and polluted condition, not less than, kVat pollution layer surface conductivity (30±3,0) мкСм150
Mass, kg38,8

Parameter names are translated from the Ukrainian catalog; the verbatim catalog wording is preserved in the data. Values are given as in the catalog, without recalculation or rounding.

Data source

IOSK catalog 2024 (in Ukrainian)

Specifications — p. 103 · Catalog numbers — p. 104 · Drawings — p. 104

Catalog numbers2 variants

Catalog numberPorcelain equivalentFlanges
P.10.150.1700.4/R.D127.4М16/0/S.D200.4х18С 4-750
upper: D Ø127 · d М16
lower: D Ø200 · d Ø18
P.10.150.1700.4/R.D127.4М16/0/S.D225.4х18С 6-750 С 8-750
upper: D Ø127 · d М16
lower: D Ø225 · d Ø18

Designation structure

Series
ИОСК
Load class (bending), kN
10
Voltage class, kV
150
Structural height, mm
1700
Atmospheric pollution degree
4

Drawings

  • Page 104

    IOSK catalog 2024 (in Ukrainian)

The drawings are in the PDF catalog on the page indicated. The source documents contain no separate image files.

Product document

ИОСК 10-150-1700-4.pdf

PDF available in Ukrainian

Open catalog PDF

Normative documents

ТУ У 31.6-31279430-007:2006 · СОУ МПЕ 40.1.51.302

Request a quote

ИОСК 10-150-1700-4

Send us a request — we will confirm the configuration, lead time and price.